FLAME DETECTOR & UV/IR DETECTOR

FLAME DETECTOR

fladet series...IH225R Triple Sensor Flame detector with IP-66 protection is specially designed to use in areas, where smoke and heat detectors are less effective. The detector makes use of both UV & IR sensors to identify the fire. It detects multiple spectral sensitivity corresponding to the fire. The intelligent signal processing enables the detector to distinguish between false source and real fire.

INSTALLATION CONSIDERATION
1.  Detector must be installed in such a way that no obstruction is on the way of sight of the detector.

2. Detector to be mounted focusing the possible fire risk area.

DETECTOR SENSITIVITY:

fladet - IH225R Triple Sensor Flame Detector can detect 1 sq.ft fire at 25mtrs. TESTED TO CONFIRM THAT, the detector can detect maximum of 50mm dia (0.0218 sq.ft) N-Heptane flame at 6 mtr in straight line, within 30 seconds (as per EN 54 requirements).

The response time of the detector depends on the size of fire, fuel type and distance of the fire source. Smaller fires and greater distances normally require more response time.

APPLICATION

Machinery production line.

Storage area

Material conveyors

Easy to Install and operate

Atriums

High roof areas

Ware -houses

Paint storage areas.

Fuel storage areas

Semi outdoor areas

Escalator areas.

storage and transfer areas.

AREA COVERAGE

1.   It has an angular coverage with cone of vision of 90 .

2.   Each detector can be considered to protect 300 m to 400 m area.

3.   However, any obstructions in the view path shall also be considered while installing the detector.

ADVANTAGES

Easy to install, operate & maintain - No special training & skill is required.

Rugged model suitable to use in Outdoor non - hazardous areas.

Readily used in environment, where other types of detectors are unsuitable.

Suitable to connect with any standard conventional fire.

Quick response to flaming fires.

4 Range of sensitivity selection.

No false or nuisance alarms.

Visual indication for alarm/normal condition.

MAINTENANCE & INSPECTION

To ensure maximum detector sensitivity, keep the surface of the optical filter (detector eye)free from dirt or other contaminants at all times.Inbuilt air purging provision is available for maintenance purpose.

TECHNICAL SPECIFICATION

PARTS SPECIFICATION
BRAND NAME fladet series
QUIESCENT CURRENT < 80mA
ALARM CURRENT < 150mA
RELAY CONTACT RATING 1A at24VDC, 0.5A at120VAC
CABLE ENTRY M20 X1.5 - 3 Nos.
PROTECTION CLASS IP-66
SENSING ELEMENT UV & IR
RANGE UV : 185-260nm
IR : 3000-5000nm
INDICATION NORMAL-FLICKERING GREEN LED FIRE -RED LED
OPERATING TEMPERATURE -20Deg.C to +60Deg.C
SUPPLY 24VDC ± 20%(RESETTABLE)
OUTPUT

1. ONE SET OF 'NO-COM-NC' CONTACT FOR FIRE + ONE SET OF DUPLICATE 'NO-COM-NC' CONTACT.

2. ONE SET OF 'NO-COM-NC' CONTACT FOR FAULT + ONE SET OF DUPLICATE 'NO-COM-NC' CONTACT.

3. ZONE DETECTOR LINE TO CONNECT DIRECTLY STANDARD CONVENTIONAL FIRE ALARM PANEL.

MATERIAL CAST ALUMINIUM LM6
FASTENERS SS 304
CERTIFICATION

1. IP PROTECTION CERTIFIED BY ETDC.

2. CONFIRMING REQUIREMENT TOEN 54-10.

3. CONFIRMING REQUIREMENT TO IS-2189.

4. CONFIRMING REQUIREMENT TO FM STANDARDS CLASS NO. 3260.

SENSITIVITY SELECTION RANGE OF SELECTION

1. LOW SENSITIVITY.

2. NORMAL SENSITIVITY (DEFAULT SETTING).

3. HIGH SENSITIVITY.

4. VERY HIGH SENSITIVITY.

ACCESSORIES

1. SWIVEL MOUNTING BASE - IH-MB-01-XY - 01 NO.

CABLE GLANDS - 2 NOS.

USER MANUAL