fladet series...IH225R Triple Sensor Flame detector with IP-66 protection is specially designed to use in areas, where smoke and heat detectors are less effective. The detector makes use of both UV & IR sensors to identify the fire. It detects multiple spectral sensitivity corresponding to the fire. The intelligent signal processing enables the detector to distinguish between false source and real fire.
INSTALLATION CONSIDERATION
1. Detector must be installed in such a way that no
obstruction is on the way of sight of the detector.
2. Detector to be mounted focusing the possible fire risk area.
fladet - IH225R Triple Sensor Flame Detector can detect 1 sq.ft fire at 25mtrs. TESTED TO CONFIRM THAT, the detector can detect maximum of 50mm dia (0.0218 sq.ft) N-Heptane flame at 6 mtr in straight line, within 30 seconds (as per EN 54 requirements).
The response time of the detector depends on the size of fire, fuel type and distance of the fire source. Smaller fires and greater distances normally require more response time.
1. It has an angular coverage with cone of vision of 90 .
2. Each detector can be considered to protect 300 m to 400 m area.
3. However, any obstructions in the view path shall also be considered while installing the detector.
To ensure maximum detector sensitivity, keep the surface of the optical filter (detector eye)free from dirt or other contaminants at all times.Inbuilt air purging provision is available for maintenance purpose.
PARTS | SPECIFICATION |
---|---|
BRAND NAME | fladet series |
QUIESCENT CURRENT | < 80mA |
ALARM CURRENT | < 150mA |
RELAY CONTACT RATING | 1A at24VDC, 0.5A at120VAC |
CABLE ENTRY | M20 X1.5 - 3 Nos. |
PROTECTION CLASS | IP-66 |
SENSING ELEMENT | UV & IR |
RANGE | UV : 185-260nm IR : 3000-5000nm |
INDICATION | NORMAL-FLICKERING GREEN LED FIRE -RED LED |
OPERATING TEMPERATURE | -20Deg.C to +60Deg.C |
SUPPLY | 24VDC ± 20%(RESETTABLE) |
OUTPUT | 1. ONE SET OF 'NO-COM-NC' CONTACT FOR FIRE + ONE SET OF DUPLICATE 'NO-COM-NC' CONTACT. 2. ONE SET OF 'NO-COM-NC' CONTACT FOR FAULT + ONE SET OF DUPLICATE 'NO-COM-NC' CONTACT. 3. ZONE DETECTOR LINE TO CONNECT DIRECTLY STANDARD CONVENTIONAL FIRE ALARM PANEL. |
MATERIAL | CAST ALUMINIUM LM6 |
FASTENERS | SS 304 |
CERTIFICATION | 1. IP PROTECTION CERTIFIED BY ETDC. 2. CONFIRMING REQUIREMENT TOEN 54-10. 3. CONFIRMING REQUIREMENT TO IS-2189. 4. CONFIRMING REQUIREMENT TO FM STANDARDS CLASS NO. 3260. |
SENSITIVITY SELECTION | RANGE OF SELECTION 1. LOW SENSITIVITY. 2. NORMAL SENSITIVITY (DEFAULT SETTING). 3. HIGH SENSITIVITY. 4. VERY HIGH SENSITIVITY. |